APPLICATIONNOTEAN‐BEI‐E2‐038 Date:15/02/12
AN‐BEI‐E2‐038ModbusRTUControlandRegisterMapping
3
MemoryMap:
Table1:Controlandstatusregisters
Note:AllregistersareHoldingRegisters
Register
Number
Parameter
Number
Upperbyte LowerByte Format Min Max Command Type Scaling
1*‐ ControlWord WORD 0 15 03,06 R/W SeeBelow
2*‐ FrequencySetpoint S16 0 5000 03,06 R/W 1dp,e.g.100=10.0Hz
3*‐ Reserved‐‐‐03,06 R/W
4*‐
Modbusrampcontroltime
U16 0 60000 03,06 R/W 2dp,e.g.500=5.00s
5‐ Reserved‐‐‐03 R
6*‐ Errorcode Drivestatus ‐‐‐03 R SeeBelow
7*‐ OutputFrequency S16 0 5000 03 R 1dp,e.g.100=10.0Hz
8*‐ MotorCurrent U16 0 ‐ 03 R 1dp,e.g.100=10.0A
9*‐ Reserved‐‐‐03 R
10‐ Reserved‐‐‐03 R
11 P00‐04 DigitalInputStatus WORD 0000 1111 03 R SeeBelow
12 P00‐20 RatingID U16 ‐‐ 03 R InternalValue
13 P00‐20 Powerrating U16 ‐‐ 03 R 2dp,e.g.37=0.37kW/HP
14 P00‐20 Voltagerating U16 ‐‐ 03 R SupplyVoltage
15 P00‐18 IOprocessorsoftwareversion U16 ‐‐ 03 R 2dp,e.g.103=1.03
16 P00‐18 Motorcontrolprocessorsoftwareversion U16 ‐‐ 03 R 2dp,e.g.103=1.03
17 P00‐20 Drivetype U16 ‐‐ 03 R InternalCode
18‐ Reserved‐‐‐03 R
19‐ Reserved‐‐‐03 R
20 P00‐01 Analog1inputresult U16 0 1000 03 R 1dp,e.g.500=50.0%
21 P00‐02 Analog2inputresult U16 0 1000 03 R 1dp,e.g.500=50.0%
22 P00‐03 Speedreferencevalue S16 0 5000 03 R 1dp,e.g.500=50.0Hz
23 P00‐08 DCbusvoltages U16 0 1000 03 R 600=600Volts
24 P00‐09 Drivetemperature S16 ‐10 150 03 R 50=50°C
25to30‐ Reserved‐‐‐03 R
*Whenusingtheexternalfieldbusgateways(PROFIBUS,DEVICENET,ETHERNET)theseregistersareavailable.
Format
WORD=WORDFormat,functionsassignedtoindividualbits
S16=Signed16BitInteger
U16=Unsigned16bitInteger