Technical Data
Beijer Electronics, MAEN772C 13
3Technical Data
Parameter EXTER T70
Front panel, W x H x D 219 x 154 x 6 mm
Mounting depth 56 mm (156 mm including clearance)
Front panel seal IP 66
Rear panel seal IP 20
Keyboard material/
Front panel
Touch screen: Polyester on glass, 1 million finger touch
operations. Overlay: Autotex F157 or F207 *.
Reverse side material Powder-coated aluminum
Weight 1.2 kg
Serial port RS422/
RS485
25-pin D-sub contact, chassis-mounted female with
standard locking screws 4-40 UNC.
Serial port RS232C 9-pin D-sub contact, male with standard locking screws 4-40
UNC.
Ethernet Shielded RJ 45
USB Host type A (USB 1.1), max output current 500mA
Device type B (USB 1.1)
CF-slot Compact flash, type I and II
Flash memory for
application
12 MB (incl. fonts)
Real time clock ±20 PPM + error because of ambient temperature and supply
voltage. Total maximum error: 1 min/month at 25 °C
Temperature coefficient: 0.004 ppm/°C
2
Real time clock
battery
CR2450 (UL and cUL: Sanyo or Panasonic)
Minimum lifetime: 3 years
Power consumption at
rated voltage
Normal: 0.4 A
Maximum: 0.9 A
Display TFT-LCD. 640 x 480 pixels, 64K color.
CCFL backlight lifetime at the ambient temperature of
+25 °C: >50,000 h.
Active area of display,
W x H
131.5 x 98.6 mm
Fuse Internal DC fuse, 3.15 AT, 5 x 20 mm
Power supply +24V DC (20 - 30V DC). Power supply connector.
CE: The power supply must conform with the requirements
according to IEC 60950 and IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class II power supplies.
Ambient temperature Vertical installation: 0 ° to +50 °C
Horizontal installation: 0 ° to +40 °C
Storage temperature -20 ° to +70 °C
Relative humidity 5 - 85 % non-condensed
CE approvals Noise tested according to EN61000-6-4 emission and
EN61000-6-2 immunity.
UL, cUL approvals
(when procuct or
packing is marked)
UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only
DNV Yes
NEMA 4x indoor use only
* See section Chemical Resistance for more information.