4.10.7. “STO“ElectricalInstallation
The“STO”wiringshallbeprotectedfrominadvertentshortcircuitsortampering whichcouldleadtofailureofthe“STO”inputsignal,
furtherguidanceisgiveninthediagramsbelow.
Inadditiontothewiringguidelinesforthe“STO”circuitbelow,section4.1.1“RecommendedinstallationforEMCcompliance.shouldalso
be
followed.
Thedriveshouldbewiredasillustratedbelow;the24Vdcsignalsourceappliedtothe“STO”inputcanbeeitherfromthe24Vdconthedriveor
fromanExternal24Vdcpowersupply.
4.10.7.1. Recommended“STO”wiring
UsinganExternal24VdcPowerSupply. Usingthedrivesonboard24Vdcsupply

TwistedPair
Shieldedcables
1213
0V
+24Vdc
Safetyrelay
ProtectiveCappedTrunking
orequivalenttoprevent
STOCableshortcircuittoan
externalVoltagesource.
External
Power
Supply



Note:TheMaximumcablelengthfromVoltagesourcetothedriveterminalsshouldnotexceed25mtrs.
4.10.8. ExternalPowersupplySpecification.
VoltageRating(Nominal) 24Vdc
STOLogicHigh 1830Vdc(Safetorqueoffinstandby)
CurrentConsumption(Maximum) 100mA
4.10.9. SafetyRelaySpecification.
Thesafetyrelayshouldbechosensothatatminimumitmeetsthesafetystandardsinwhichthedrivemeets.
StandardRequirements SIL2orPLdSC3orbetter(WithForciblyguidedContacts)
NumberofOutputContacts 2independent
SwitchingVoltageRating 30Vdc
SwitchingCurrent 100mA
Wiresshouldbe
protected
againstshort
circuitsas
shownabove
Przeglądanie stron 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 55 56

Komentarze do niniejszej Instrukcji

Brak uwag

JBL Altoparlanti/dockin station manuali utente

Partendo da A

Cliccare su un alfabeto di seguito per far scorrere la lista completa dei modellif models starting with that letter

Modelli Tipo di Documento
AIR
Manuale del Proprietario   JBL OnBeat Air, 15 pagine