10. TechnicalData
10.1. Environmental
Ambienttemperaturerange Operational :‐1050°C(IP20Units),40°C(IP55Units),30°C(IP55,90kW/150HPunits)
Storage :‐40°C60°C
Maxaltitudeforratedoperation :1000m
Deratingabove1000m(to4000mmax) :1%/100m
RelativeHumidity:
<95%(noncondensing)
Note : DrivemustbeFrostandmoisturefreeatalltimes
Installationabove2000misnotULapproved
10.2. Input/OutputPowerandCurrentratings
Thefollowingtablesprovidetheoutputcurrentratinginformationforthevariousdrivemodels.Itisalwaysrecommendthattheselectionofthe
correctdriveisbaseduponthe motorfullloadcurrentattheincomingsupplyvoltage.
200‐240Volt(+/‐10%)1PhaseInput,3PhaseOutput
kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Input Or Cable Output Cable Motor Brake
Current MCB(TypeB) Size Current Size Cable Resistance
 NonUL UL mm AWG/kcmilmm AWG LengthΩ
0.75 1 10.5 16 15 2.5 12 4.3 1.5 14 100 100
1.5 2 16.2 20 20 4 10 7 1.5 14 100 50
2.2 3 23.8 25 25 10 8 10.5 1.5 14 100 35
Note
Ratingsshownaboveapplyto40°CAmbienttemperature.Forderatinginformation,refertosection10.4
Themaximummotorcablelengthstatedappliestousingashieldedmotorcable.Whenusinganunshieldedcable,themaximumcablelength
limitmaybeincreasedby50%.Whenusingtherecommendedoutputchoke,
themaximumcablelengthmaybeincrease dby100%
ThePWMoutputswitchingfromanyinverterwhenusedwithalongmotorcablelengthcancauseanincreaseinthevoltageatthemotor
terminals,dependingonthemotorcablelengthandinductance.Therisetimeandpeakvoltage
canaffecttheservicelifeofthe motorBeijer
Electronicsrecommendusinganoutputchokeformotorcablelengthsof50mormoretoensuregoodmotorservicelife
ForULcompliantinstallation,useCopperwirewithaminimuminsulationtemperatureratingof70°C,ULClassCCorClassJ
Fuses
200‐240Volt(+/‐10%)3PhaseInput,3PhaseOutput
kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Input Or Cable Output Cable Motor Brake
Current MCB(TypeB) Size Current Size Cable Resistance
 NonUL UL(A) mm AWG/kcmilmm AWG/kcmil LengthΩ
0.75 1 3.7 10 6 1.5 14 4.3 1.5 14 100 100
1.5 2 5.9 10 10 1.5 14 7 1.5 14 100 50
2.2 3 7.9 10 10 1.5 14 10.5 1.5 14 100 35
4 5 16.3 25 25 4 10 18 2.5 10 100 20
5.5 7.5 22.5 32 30 6 10 24 4 10 100 20
7.5 10 32.9 50 45 16 8 30 6 8 100 22
11 15 54.1 80 70 25 4 46 10 6 100 22
15 20 69.6 100 90 35 3 61 16 4 100 12
18.5 25 76.9 100 100 35 3 72 25 3 100 12
22 30 92.3 125 125 50 1 90 35 2 100 6
30 40 116.9 160 150 70 1/0 110 50 1/0 100 6
37 50 150.2 200 200 95 3/0 150 70 3/0 100 6
45 60 176.5 250 225 120
4/0
180 95 4/0 100 6
55 75 211 300 300 185 300 202 120 250 100 6
75 120 267 400 350 2x95 400 248 150 350 100 6
Note
Ratingsshownaboveapplyto40°CAmbienttemperature.Forderatinginformation,refertosection10.4
Themaximummotorcablelengthstatedappliestousingashieldedmotorcable.Whenusinganunshieldedcable,themaximumcablelength
limitmaybeincreasedby50%.Whenusingtherecommendedoutputchoke,
themaximumcablelengthmaybeincrease dby100%
ThePWMoutputswitchingfromanyinverterwhenusedwithalongmotorcablelengthcancauseanincreaseinthevoltageatthemotor
terminals,dependingonthemotorcablelengthandinductance.Therisetimeandpeakvoltage
canaffecttheservicelifeofthe motor.Beijer
Electronicsrecommendusinganoutputchokeformotorcablelengthsof50mormoretoensuregoodmotorservicelife
ForULcompliantinstallation,useCopperwirewithaminimuminsulationtemperatureratingof70°C,ULClassCCorClassJ
Fuses