Beijer-electronics BFI-P2 V1.21 Instrukcja Użytkownika Strona 39

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 38
UserGuideRevision1.121
www.beijerelectronics.com
39
Par ParameterName Minimum Maximum Default Units
P221 DisplayScalingFactor 30.000 30.000 0.000 ‐
P222 DisplayScalingSource 0 2 0 ‐
P221&P222allowtheusertoprogramtheDrivetodisplayanalternativeoutputunitscaledfromanexistingparameter,e.g.to
displayconveyerspeedinmetrespersecondbasedontheoutputfrequency.ThisfunctionisdisabledifP221issetto0.
IfP221
isset>0,thevariableselectedinP222ismultipliedbythefactorenteredinP221,anddisplayedwhilstthe driveis
running,witha‘c’toindicatethecustomerscaledunits.
P222Options
0:MotorSpeed
1:MotorCurrent
2:AnalogInput2
3:P080Value
P223 ZeroSpeedHoldingTime 0.0 60.0 0.2 Seconds
Determinesthetimeforwhichthedriveoutputfrequencyisheldatzerowhenstopping,beforethedriveoutputisdisabled
P224 EffectiveSwitchingFrequency DriveRatingDependent kHz
Effectivepowerstageswitchingfrequency.Therangeofsettingsavailableandfactorydefaultparametersettingdependonthe
drivepowerandvoltagerating.Higherfrequenciesreducetheaudible‘ringing’noisefromthemotor,andimprovetheoutput
currentwaveform,attheexpenseofincreaseddrivelosses.Refertosection1Error!Referencesourcenotfound..4forfurther
informationregardingoperationathigherswitchingfrequency.
P225 2ndDecelerationRampTime 0.00 240.0 0.00 Seconds
ThisparameterallowsanalternativedecelerationrampdowntimetobeprogrammedintotheDrive,whichcanbeselectedby
digitalinputs(dependentonthesettingofP113)orselectedautomaticallyinthecaseofamainspowerlossifP238=2.
Whensetto0.0,thedrivewillcoasttostop.
P226 SpinStartEnable 0 1 0 ‐
0:Disabled
1:Enabled.Whenenabled,onstartupthedrivewillattempttodetermineifthemotorisalreadyrotating,andwillbegintocontrol
themotorfromitscurrentspeed.Ashortdelaymaybeobservedwhenstartingmotorswhicharenotturning.
P227 StandbyModeTimer 0.0 250.0 0.0 Seconds
Thisparameterdefinestimeperiod,wherebyifthedriveoperatesatminimumspeedforatleastthesettimeperiod,theDrive
outputwillbedisabled,andthedisplaywillshowstndby.ThefunctionisdisabledifP227=0.0.
P228 SlaveSpeedScalingControl 0 3 0 ‐
ActiveinKeypadmode(P112=1or2)andSlavemode(P112=5)only.Thekeypadreferencecanbemultipliedbyapresetscaling
factororadjustedusingananalogtrimoroffset.
0:Disabled.Noscalingoroffsetisapplied.
1:ActualSpeed=Digital
SpeedxP229
2:ActualSpeed=(DigitalSpeedxP229)+AnalogInput1Reference
3:ActualSpeed=(DigitalSpeedxP229)xAnalogInput1Reference
P229 SlaveSpeedScalingFactor 500.0 500.0 100.0 %
UsedinconjunctionwithP228.
P230 AnalogInput1(Terminal6)Format SeeBelow
U 0-10
‐
U 0-10=0to10VoltSignal(Unipolar)
U 10-0=10to0VoltSignal(Unipolar)
-10-10=‐10to+10VoltSignal(Bipolar)
A 0-20=0to20mASignal
t 4-20=4to20mASignal,theDrivewilltripandshowthefaultcode4-20Fifthesignallevelfallsbelow3mA
r 4-20=4to20mASignal,theDrivewillramptostopifthesignallevelfallsbelow3mA
t 20-4=20to4mASignal,theDrivewilltripandshowthefaultcode4-20Fifthe signallevelfallsbelow3mA
r 20-4=20
to4mASignal,theDrivewillramptostopifthesignallevelfallsbelow3mA
P231 AnalogInput1Scaling 0.0 500.0 100.0 %
Scalestheanaloginputbythisfactor,e.g.ifP230issetfor010V,andthescalingfactorissetto200.0%,a5voltinputwillresult
inthedriverunningatmaximumspeed(P101)
P232 AnalogInput1Offset 500.0 500.0 0.0 %
Setsanoffset,asapercentageofthefullscalerangeoftheinput,whichisappliedtotheanaloginputsignal